●Features:
● Small Size — L × W × H, mm: 81 × 18 (Per Pole) × 75
● DIN Rail Mount
● Two Trip Curves: C — 7-10 Times Rating; D — 10-14 Times Rating
● Positive Indication of Contact Disconnect
●Applications Permitting Supplementary Protectors:
● Supplements or Provides Additional Protection for Sensitive Electronics Inside the Equipment
● Used on the Load Side of Branch Circuit Protection to Protect Criteria or Sensitive Internal Circuitry Such as: Computers and Microprocessors, Communications Equipment, Electronic Controllers and Power Supplies
● Permitted for Protection of Motor Control Circuits NEC 430-72, Unless Transformers Are in Circuit, Then UL 489
●Specifications:
● Ampere Ratings: From 0.5 to 63 Amps
● 10K Air @ 120/240 VAC; 5K Air @ 480Y/277 VAC
● DC Ratings (C-Curve Only): 1-Pole — 60 VDC; 2-Pole — 125 VDC