Part Datasheet Search > AC/DC Converters > XP Power > AFM30US18 Datasheet PDF > AFM30US18 Datasheet Pages 1/2
AFM30US18Datasheet PDF
Page:
of 2 Go
If the format of the manual is confusing, please download and read the original PDF file.
AC-DC
Specification
30-60 Watts
• Energy Efficiency Level V
• CEC2008 & EISA2007 Compliant
• I
T & Medical Approvals
• China Compulsory Certification (CCC) Qualified
• Optional Class II Versions
• Optional White Case Versions
• 3 Year Warranty
AFM Series
Input
Input Voltage • 80-264 VAC, derate output power 25%
<90 VAC
Input Frequency • 47-63 Hz
Input Current • AFM30: 0.8 A rms at 115VAC,
AFM45: 1.2 A rms at 115VAC,
AFM60: 1.5 A rms at 115 VAC
Inrush Current • AFM30: 50 A max at 240VAC,
AFM45: 50 A max at 240VAC,
AFM60: 120 A max at 240VAC
Power Factor • EN61000-3-2, class A
Earth Leakage Current • 150 µA max at 264 VAC/60 Hz
No Load Input Power • AFM30/45: <0.3 W, AFM60: <0.5 W
Output
Output Voltage • See table
Output Voltage Trim • Not user-adjustable
Initial Set Accuracy • ±2%
Minimum Load • No minimum load required
Start Up Delay • 3 s max at 115 VAC
Hold Up Time • 8 ms minimum at 115 VAC
Line Regulation • ±1.0% maximum
Load Regulation • 2.5% maximum
Transient Response • 4% max. deviation, recovery to within
1% in 500 µs for a 25% load change
Ripple & Noise • 1% max pk-pk
(1)
Overvoltage Protection • 110-170% Vnom, recycle input to reset
Overload Protection • AFM45/60: 110-170%,
AFM30: 110-220%, auto recovery
Short Circuit Protection • Trip and restart (hiccup mode)
Temperature • 0.04%/°C
Coefficient
xppower.com
General
Efficiency • See table
Energy Efficiency • Level V
Isolation • 4000 VAC Input to Output, 2 x MOPP
1500 VAC Input to Ground, 1 x MOPP*
Output 0 V is electrically connected to
Input Ground*. *Not C8 version.
Switching Frequency • 30/45 W: 58 kHz typ., 60 W: 52 kHz typ.
Power Density • AFM30: 2.8 W/In
3
, AFM45: 4.2 W/In
3
,
AFM60: 3.76 W/In
3
MTBF • >250 kHrs to MIL-HDBK-217F at 25 °C,
GB, full load
Environmental
Operating Temperature • 0 °C to +60 °C, derate from 100% power
at +40 °C to 60% power at +60 °C
Operating Humidity • 10-95% RH, non-condensing
Storage Temperature • -40 °C to +80 °C
Operating Altitude • 2000 m
Shock • 30 g, 10 ms on 3 axes
Vibration • 5-100 Hz, 2.31 m/s
2
, 20 mins, 3 axes
EMC & Safety
Emissions • EN55011/22/FCC Class B conducted,
EN55011/22/FCC Class B radiated
Harmonic Currents • EN61000-3-2, Class A
Voltage Flicker • EN61000-3-3
ESD Immunity • EN61000-4-2, 6 kV contact and
8 kV air discharge
Radiated Immunity • EN61000-4-3, 3 V/m Perf Criteria A
EFT/Burst • EN61000-4-4, level 3 Perf Criteria A
(7)
Surge • EN61000-4-5, installation class 3
Perf Criteria A
Conducted Immunity • EN61000-4-6, 3 Vrms Perf Criteria A
Magnetic Field • EN61000-4-8, 3 A/m, Perf Criteria A
Dips & Interruptions • EN61000-4-11, 30% for 10 ms,
60% 100 ms, 100% 5000 ms,
Perf Criteria A, B, B
EN60601-1-2, 30% 500 ms, 60% 100 ms,
100% 10 ms, 100% 5000 ms,
Perf A, A, A, B
(8)
Safety Approvals • EN60950-1, UL60950-1, IEC60950-1
EN60601-1 (3rd Ed.), UL60601-1 (2nd Ed.),
IEC60601-1 (3rd Ed.) China Compulsory
Certification (CCC) Qualified.