Part Datasheet Search > Schneider Electric > ATS22D47Q Datasheet PDF > ATS22D47Q Other Datasheet PDF Pages 1/10
ATS22D47Q
Price from AiPCBA
ATS22D47QDatasheet PDF
Page:
of 10 Go
If the format of the manual is confusing, please download and read the original PDF file.
The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the products contained herein.
This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications.
It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products with respect to the relevant specific application or use thereof.
Neither Schneider Electric Industries SAS nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the information contained herein.
10/8/2011
1
Product data sheet
Characteristics
ATS22D47Q
soft starter-ATS22-control 220V-power
230V(11kW)/400...440V(22kW)
Main
Range of product Altistart 22
Product or component
type
Soft starter
Product destination Asynchronous motors
Product specific
application
Severe and standard applications
Component name ATS22
Network number of
phases
3 phases
Power supply voltage 230...440 V (- 15...10 %)
Motor power kW 11 kW at 230 V
22 kW at 400 V
22 kW at 440 V
Factory setting current 42 A
Power dissipation in W 48 W for standard applications
Utilisation category AC-53A
Type of start Start with torque control (current limited to 3.5 In)
Icl nominal current 47 A (connection in the motor supply line) for
standard applications
IP degree of protection IP20
Complementary
Assembly style With heat sink
Function available Internal bypass
Power supply voltage limits 195...484 V
Power supply frequency 50...60 Hz (- 10...10 %)
Network frequency 45...66 Hz
Device connection In the motor supply line
To the motor delta terminals
Control circuit voltage 220...230 V -15...10 % at 50/60 Hz
Control circuit consumption 20 W
Discrete output number 2
Discrete output type (R1)Relay outputs 230 V running, alarm, trip, stopped, not stopped, starting,
ready, C/O
(R2)Relay outputs 230 V running, alarm, trip, stopped, not stopped, starting,
ready, C/O
Minimum switching current Relay outputs 100 mA at 12 V, DC
Maximum switching current Relay outputs 5 A at 250 V, AC resistive load, cos phi = 1
Relay outputs 5 A at 30 V, DC resistive load, cos phi = 1
Relay outputs 2 A at 250 V, AC inductive load, cos phi = 0.4, L/R = 20 ms
Relay outputs 2 A at 30 V, DC inductive load, L/R = 7 ms
Discrete input number 3
Discrete input type (LI1, LI2, LI3)logic 5 mA 4.3 kOhm
Discrete input voltage 24 V (<= 30 V)
Discrete input logic (LI1, LI2, LI3)positive logic state 0 < 5 V and < 2 mA state 1 > 11 V and > 5 mA
Output current 0.4...1 Icl adjustable
PTC probe input 750 Ohm
Communication port protocol Modbus
Connector type 1 RJ45
Communication data link Serial
Physical interface RS485 multidrop

ATS22D47Q Documents

Schneider Electric
1 Pages / 0.05 MByte
Schneider Electric
85 Pages / 3.51 MByte
Schneider Electric
10 Pages / 0.21 MByte

ATS22D47 Documents

Schneider Electric
Soft Start, 208 - 600VAC, 110V Cntrl, 47A, 15HP at 230V
Schneider Electric
Soft Starter, Asynchronous Motors, Altistart 22 Series, Three Phase, 22kW, 47A, 230V to 440V
Schneider Electric
47A Soft Starter ATS22 Series, IP54, 30kW, 208 - 600V
Part Datasheet PDF Search
72,405,303 Parts Datasheet PDF, Update more than 5,000 PDF files ervery day.