Part Datasheet Search > I/O Modules > Schneider Electric > TM3DI16 Datasheet PDF > TM3DI16 Datasheet Pages 1/12
TM3DI16
Price from AiPCBA
TM3DI16Datasheet PDF
Page:
of 12 Go
If the format of the manual is confusing, please download and read the original PDF file.
The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the products contained herein.
This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications.
It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products with respect to the relevant specific application or use thereof.
Neither Schneider Electric Industries SAS nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the information contained herein.
Jul 31, 2014
1
Product data sheet
Characteristics
TM221CE40R
controller M221 40 IO relay Ethernet
Main
Range of product Modicon M221
Product or component
type
Logic controller
[Us] rated supply volt-
age
100...240 V AC
Discrete input number 24 discrete input conforming to IEC 61131-2 Type 1
including 4 fast input
Analogue input number 2 at input range: 0...10 V
Discrete output type Relay normally open
Discrete output number 16 relay
Discrete output voltage 5...250 V AC
5...125 V DC
Discrete output current 2 A
Complementary
Discrete I/O number 40
Number of I/O expansion module <= 7 with <= 48 discrete output(s) for relay output
Supply voltage limits 85...264 V
Network frequency 50/60 Hz
Inrush current <= 40 A
Power consumption in VA <= 70 VA at 100...240 V
Discrete input logic Sink or source (positive/negative)
Discrete input voltage 24 V
Discrete input voltage type DC
Analogue input resolution 10 bits
LSB value 10 mV
Conversion time 1 ms per channel + 1 controller cycle time for analog input
Permitted overload on inputs +/- 15 V DC for analog input permanent
+/- 30 V DC for analog input with 5 min maximum
Voltage state1 guaranteed >= 15 V for input
Current state 1 guaranteed >= 2.5 mA for input
Voltage state 0 guaranteed <= 5 V for input
Current state 0 guaranteed <= 1 mA for input
Discrete input current 7 mA for input
Input impedance 100 kOhm for analog input
3.4 kOhm for discrete input
Response time 10 ms turn-off operation for output
10 ms turn-on operation for output
5 µs turn-off operation for fast input
5 µs turn-on operation for fast input
100 µs turn-off operation for input; I8...I15 terminal
100 µs turn-on operation for input; I8...I15 terminal
35 µs turn-off operation for input; I2...I5 terminal
35 µs turn-on operation for input; I2...I5 terminal
Configurable filtering time 12 ms for input
3 ms for input
0 ms for input
Output voltage limits 277 V AC
125 V DC
Current per output common 8 A
Absolute accuracy error +/- 1 % of full scale for analog input

TM3DI16 Documents

Schneider Electric
12 Pages / 0.25 MByte
Schneider Electric
5 Pages / 5.69 MByte
Part Datasheet PDF Search