Part Datasheet Search > Uncategorized > Schneider Electric > RM17UAS14 Datasheet PDF > RM17UAS14 Datasheet Pages 1/6
RM17UAS14Datasheet PDF
Page:
of 6 Go
If the format of the manual is confusing, please download and read the original PDF file.
The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the products contained herein.
This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications.
It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products with respect to the relevant specific application or use thereof.
Neither Schneider Electric Industries SAS nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the information contained herein.
Jan 9, 2013
1
Product data sheet
Characteristics
RM17UAS16
voltage control relay RM17-U - range 20..80 V
AC
Main
Range of product Zelio Control
Product or component
type
Modular measurement and control relays
Relay type Voltage control relay
Product specific appli-
cation
For single-phase and DC supply
Relay name RM17UAS
Relay monitored pa-
rameters
Overvoltage or undervoltage detection
Self-powered
Time delay Adjustable 0.1...10 s, 0 + 10 % on crossing the
threshold
Switching capacity in
VA
1250 VA
Minimum switching cur-
rent
10 mA at 5 V DC
Maximum switching
current
5 A AC/DC
Power consumption in
VA
<= 3.9 VA AC
Measurement range 20...80 V voltage DC
20...80 V voltage AC 50/60 Hz
Electrical connection 2 conductors cable 0.5...2.5 mm² AWG20...AWG14
solid cablewithout cable end conforming to IEC
60947-1
2 conductors cable 0.2...1.5 mm² AWG24...AWG16
flexible cablewith cable end conforming to IEC
60947-1
1 conductor cable 0.5...4 mm² AWG20...AWG11 sol-
id cablewithout cable end conforming to IEC 60947-1
1 conductor cable 0.2...2.5 mm² AWG24...AWG12
flexible cablewith cable end conforming to IEC
60947-1
Utilisation category DC-14 conforming to IEC 60947-5-1
DC-13 conforming to IEC 60947-5-1
DC-12 conforming to IEC 60947-5-1
AC-15 conforming to IEC 60947-5-1
AC-14 conforming to IEC 60947-5-1
AC-13 conforming to IEC 60947-5-1
AC-12 conforming to IEC 60947-5-1
Complementary
Reset time 1500 ms for time delay
Maximum switching voltage 250 V AC/DC
[Us] rated supply voltage 24...48 V AC/DC
Supply voltage limits 15...100 V AC/DC
Power consumption in W <= 1.6 W DC
Control circuit frequency 50...60 Hz +/- 10 %
Output contacts 1 C/O
Nominal output current 5 A
Measuring cycle <= 150 ms measurement cycle as true rms value
Hysteresis 5...20 % of threshold setting
Delay at power up <= 500 ms AC
<= 100 ms DC
Measurement accuracy +/- 10 % of the full scale value