Manufacturer: | Schneider Electric |
Description: | Multi-Delay Relay, SPDT, Momentary, 0.004A (Coil), 240VDC (Coil), 1000mW (Coil), 5A (Contact), 250VDC (Contact), 0.1s Adj Min, 10s Adj Max, AC-DC Input, AC-DC Output, DIN-Rail Mount |
Pictures: |
RM17UBE15Datasheet PDF
Page:
of 5 Go
If the format of the manual is confusing, please download and read the original PDF file.
The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the products contained herein.
This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications.
It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products with respect to the relevant specific application or use thereof.
Neither Schneider Electric Industries SAS nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the information contained herein.
7/9/2011
1
Product data sheet
Characteristics
RM17UBE15
voltage control relay RM17-U - range 65..260 V
AC/DC
Main
Range of product Zelio Control
Product or component
type
Modular measurement and control relays
Relay type Voltage control relay
Product specific
application
For single-phase and DC supply
Relay name RM17UBE
Relay monitored
parameters
Overvoltage and undervoltage detection
Self-powered
Time delay Adjustable 0.1...10 s, 0 + 10 % on crossing the
threshold
Switching capacity in
VA
1250 VA
Minimum switching
current
10 mA at 5 V DC
Maximum switching
current
5 A AC/DC
Power consumption in
VA
<= 3 VA AC
Measurement range 65...260 V voltage AC/DC
Electrical connection 1 conductor cable 0.2...2.5 mm² AWG24...AWG12
flexible cablewith cable end conforming to IEC
60947-1
1 conductor cable 0.5...4 mm² AWG20...AWG11
solid cablewithout cable end conforming to IEC
60947-1
2 conductors cable 0.2...1.5 mm² AWG24...AWG16
flexible cablewith cable end conforming to IEC
60947-1
2 conductors cable 0.5...2.5 mm² AWG20...AWG14
solid cablewithout cable end conforming to IEC
60947-1
Utilisation category AC-12 conforming to IEC 60947-5-1
AC-13 conforming to IEC 60947-5-1
AC-14 conforming to IEC 60947-5-1
AC-15 conforming to IEC 60947-5-1
DC-12 conforming to IEC 60947-5-1
DC-13 conforming to IEC 60947-5-1
DC-14 conforming to IEC 60947-5-1
Complementary
Reset time 1500 ms for time delay
Maximum switching voltage 250 V AC/DC
[Us] rated supply voltage 110...240 V AC/DC
Supply voltage limits 50...270 V AC/DC
Power consumption in W <= 1 W DC
Control circuit frequency 50...60 Hz +/- 10 %
Output contacts 1 C/O
Nominal output current 5 A
Measuring cycle <= 150 ms measurement cycle as true rms value
Hysteresis 3 % fixed of threshold setting
Delay at power up 1 s DC
0.5 s AC
Measurement accuracy +/- 10 % of the full scale value
Part Datasheet PDF Search