Part Datasheet Search > AC/DC Converters > XP Power > DNR18US15 Datasheet PDF > DNR18US15 Other Datasheet PDF Pages 1/4
DNR18US15Datasheet PDF
Page:
of 4 Go
If the format of the manual is confusing, please download and read the original PDF file.
AC-DC
Specification
5-60 Watts
• Rugged Design for Industrial Applications
• Up to 89% Efficiency
• Full Power to +60 ºC
• Wide Adjustment Range
• DC OK 24 V Models
• DC Standby Versions
• 3 Year Warranty
DNR05-60 Series
Input
Input Voltage • 90-264 VAC, 120-375 VDC (DNR05/10/18)
85-264 VAC, 90-375 VDC (DNR30/60)
Input Frequency • 47-63 Hz
Inrush Current • 5-18 W: 10/18 A at 115/230 VAC
30 W: 20/40 A at 115/230 VAC
60 W: 30/60 A at 115/230 VAC
Power Factor • Meets EN61000-3-2 for class A equipment
Earth Leakage Current • 0.8 mA max
Input Protection • Internal fuse T2A, 250 VAC
Output
Output Voltage • See tables
Output Voltage Trim • See tables
Initial Set Accuracy • ±1%
Minimum Load • No minimum load required
Start Up Delay • <1000 ms (may increase at low
temperature extremes)
Start Up Rise Time • <150 ms
Hold Up Time • 30/130 ms at 115/230 VAC (DNR05)
25/100 ms at 115/230 VAC (DNR10)
20/75 ms at 115/230 VAC (DNR18)
20/30 ms at 115/230 VAC (DNR30)
20/30 ms at 115/230 VAC DNR60)
Line Regulation • 5-18 W: ±1.0% max
30-60 W: ±0.5% max
Load Regulation • 5-18 W: ±2.0% max
30-60 W: ±0.5% max
Parallel Operation • Redundancy module DPM10 available
for load currents up to 10 A, contact sales.
Transient Response • 4% max deviation recovering to within
1% in 1 ms for a 50% load change
Ripple & Noise • 50 mV pk-pk, 20 MHz bandwidth (may
increase at low temperature extremes)
Overvoltage Protection • Output clamps at 120-145% Vnom,
auto recovery
Overload Protection • 105-145% Constant current,
105-145% Power limited (DNR30/60)
Short Circuit Protection • Power limited, auto recovery
Temperature • ±0.03%/ºC
Coefficient
xppower.com
General
Efficiency • See tables
Isolation • 3000 VAC Input to Output
1500 VAC Input to Ground
500 VAC Output to Ground
Switching Frequency • 100 KHz typical
Signals • DC ON indicator LED Green: All models
DC LOW indicator LED Red:
5-18 W models
DC OK: 24 V 30-60 W models
MTBF • 780 kHrs typical Bellcore, Issue 6
at +40 ºC, GB (DNR05/10/18)
530 kHrs typical Bellcore, Issue 6
at +40 ºC, GB (DNR30/60)
DIN Rail • Compatible with TS35/7.5 or TS35/15
Environmental
Operating Temperature • -25 °C to +70 °C, derate linearly from
+50 °C for 5 & 18 W models, +60 °C for
all other models (See derating curves)
Cooling • Convection-cooled with 25mm free space
all sides
Operating Humidity • 20-95% RH, non-condensing
Storage Temperature • -25 ºC to +85 ºC
Shock • 4 g, 22 ms, X, Y & Z axis
Vibration • 1 g, 10 Hz to 500 kHz, along X, Y & Z axis
EMC & Safety
Emissions • EN55022, level B conducted
Harmonic Currents • EN61000-3-2, class A
Voltage Flicker • EN61000-3-3 amendments 1 & 2
ESD Immunity • EN61000-4-2, level 3 Perf Criteria A
Radiated Immunity • EN61000-4-3, level 3 Perf Criteria A
EFT/Burst • EN61000-4-4, level 3 Perf Criteria A
Surge • EN61000-4-5, level 3 Perf Criteria A
Dips & Interruptions • EN61000-4-11, 30% 10 ms,
60% 100 ms, 100% 5000 ms
Perf Criteria A, B, B
Safety Approvals • EN60950-1, UL508, Pollution Degree 2,
UL1310 - see note 3 & ratings table,
UL60950-1, Overvoltage Category II,
UL508, Overvoltage Category III,
DNR30 & DNR60: SEMI F47
Part Datasheet PDF Search
72,405,303 Parts Datasheet PDF, Update more than 5,000 PDF files ervery day.